U.S. regulators of natural gas infrastructure have issued an order requiring the owner of a liquefied natural gas terminal in Louisiana to remove part of that facility from service, following the discovery of unintended releases of LNG from the facility.
At issue is Sabine Pass Liquefaction, LLC's Sabine Pass Liquefaction Facility. The company is a subsidiary of Cheniere Energy, Inc. The Sabine Pass LNG terminal includes five
LNG storage tanks with capacity of approximately 16.9 billion cubic feet
equivalent (Bcfe), two marine berths that can accommodate vessels with
nominal capacity of up to 266,000 cubic meters and vaporizers with
regasification capacity of approximately 4.0 Bcf/d, adjacent to a series of liquefaction trains. The facility has received U.S. Department of Energy authorization for export of LNG by vessel.
According to a Corrective Action Order issued by the Pipeline and Hazardous Materials Safety Administration on February 8, 2018, on
January
22,
2018,
workers
at the Sabine Pass plant discovered
a
release
of LNG from a storage tank at the facility. The order states that LNG escaped from the tank into the annulus -- the space between the tank's inner and outer walls -- which eventually caused cracks in the outer tank wall and the pooling of LNG in a secondary containment area. It also says that the federal investigation into this incident discovered additional LNG releases from multiple cracks in another tank at the site, with evidence of "brittle failures" in the carbon steel outer tank wall.
The order says Sabine took steps upon discovery of the incident including commencing de-inventorying LNG from the tank, reducing system pressures, and deploying an emergency management team. Sabine reported no injuries or fatalities as a result of the incident, and there were no reported fires or explosions. The cause of the incident has not yet been determined.
The PHMSA order requiring corrective action includes a finding "that
the
continued
operation
of
the
Affected
Tanks
without
corrective
measures
is
or
would
be
hazardous
to
life,
property
and
the
environment." It describes unintended
releases
of
LNG
as "rare ... low
-frequency,
high-consequence"
events which "can
result
in
a
serious
hazard
to
people
and
property." It notes, "To
date,
Sabine
has
been
unable
to
correct
the
long-standing
safety
concerns
described
above
involving
the
Affected
Tanks,
cannot
validate
the
exact
source
or
amount
of
the
LNG
that
may
have
leaked
into
the
annulus
of
the
Affected
Tanks,
and
cannot
identify
the
circumstances
that
allowed
the
LNG
to
escape
containment
in
the
first
place."
The order requires Sabine to develop a timeline and plan for removing the two "Affected Tanks" and their associated systems from service. A third tank is described in a footnote to the order as having experienced releases of LNG from the inner tank into the annular space, but is not included as one of the "Affected Tanks" covered by the order requiring corrective action. It requires Sabine to develop a work-plan including tank-specific purging plans, a root-cause analysis plan, a detailed repair and modification plan, a continuing operation plan for facilities that remain in service, and a plan to return the affected tanks to service, and prohibits Sabine from returning the affected tanks to service until authorized to do so by the Director of PHMSA.